FT900-93
  • 12-volts
  • 93 Group Size
  • 160 mins @ 25 amps
  • 24 mins @ 75 amps
  • 55 AH @ 5HR
  • 70 AH @ 20HR
  • 1080 CA @ 32°C
  • 900 CCA @ 0°C
FT900-93

FT900-93 High Capacity Dual Purpose AGM Battery

Cycling Capacity
20 hour rate 70 Amp Hours
Reserve Capacity
@ 25 Amps 160 minutes @ 75 Amps 24 minutes
Mechanical Specifications
Group Size 93
Terminal Type M8
Total Height 7.05" (179 mm)
Height 7.05" (179 mm)
Width 6.57" (167 mm)
Length 13.82" (351 mm)
Weight 54.7 lbs (24.8 kg)
Case Type ABS Plastic - Flame Res Rating UL94-HB
Discharge Table (Constant Current)
Time Amps Rate
20 hr 3.5 0.05 CA
10 hr 6.4 0.1 CA
8 hr 7.6 0.13 CA
5 hr 11.8 0.25 CA
3 hr 17.5 0.33 CA
2 hr 23 0.5 CA
1 hr 41 1 CA
Electrical Specifications
Nominal Voltage 12 Volt
Capacity @ 100 hour rate 77 AH
Capacity @ 20 hour rate 70 AH
Capacity @ 10 hour rate 62 AH
Capacity @ 5 hour rate 55 AH
CCA 900
CA or MCA 1080
Short Circuit Current 3000 Amps
Internal Resistance 3.5m Ω
Charge Voltages
Battery Voltages
Charge Stage 12V 24V 36V 48V
Bulk 14.7 V 29.4 V 44.1 V 58.8 V
Absorption 14.7 V 29.4 V 44.1 V 58.8 V
Float 13.6 V 27.2 V 40.8 V 54.6 V
TC Factor: -4mV/°C/cell
Temperature Range Specifications
Condition Recommended Maximum
Storage -15°C to 50°C -40°C to 71°C
Operation -15°C to 40°C -40°C to 71°C
Charge with TC -15°C to 50°C -40°C to 71°C
Charge without TC 0°C to 40°C -15°C to 50°C
Terminal Torque Specifications
Terminal Type ft-lbs in-lbs Nm
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) 4.2 - 6.9 50-79 5.6 - 7.18
FR45 6.0 - 7.14 70-99 7.9 - 10.10
M8 | LT 7.1 - 8.9 85-104 9.6 - 10.16
DT (stud) | M10M (stud) 9.2 - 10.13 110-134 12.2 - 14.9