FT1150-6T
  • 12-volts
  • 6T Group Size
  • 273 mins @ 25 amps
  • 60 mins @ 75 amps
  • 105 AH @ 5HR
  • 120 AH @ 20HR
  • 1450 CA @ 32°C
  • 1150 CCA @ 0°C
FT1150-6T

FT1150-6T High Capacity Dual Purpose AGM Battery

Cycling Capacity
20 hour rate 120 Amp Hours
Reserve Capacity
@ 25 Amps 273 minutes @ 75 Amps 60 minutes
Mechanical Specifications
Group Size 6T
Terminal Type M8
Total Height 8.86" (225 mm)
Height 8.11" (206 mm)
Width 10.55" (268 mm)
Length 11.18" (284 mm)
Weight 85.3 lbs (38.7 kg)
Case Type ABS Plastic - Flame Res Rating UL94-HB
Discharge Table (Constant Current)
Time Amps Rate
20 hr 6 0.05 CA
10 hr 11 0.1 CA
8 hr 13.1 0.13 CA
5 hr 21 0.25 CA
3 hr 30.2 0.33 CA
2 hr 40.1 0.5 CA
1 hr 75 1 CA
Electrical Specifications
Nominal Voltage 12 Volt
Capacity @ 100 hour rate 132 AH
Capacity @ 20 hour rate 120 AH
Capacity @ 10 hour rate 114 AH
Capacity @ 5 hour rate 105 AH
CCA 1150
CA or MCA 1450
Short Circuit Current 5000 Amps
Internal Resistance 2.1m Ω
Charge Voltages
Battery Voltages
Charge Stage 12V 24V 36V 48V
Bulk 14.7 V 29.4 V 44.1 V 58.8 V
Absorption 14.7 V 29.4 V 44.1 V 58.8 V
Float 13.6 V 27.2 V 40.8 V 54.6 V
TC Factor: -4mV/°C/cell
Temperature Range Specifications
Condition Recommended Maximum
Storage -15°C to 50°C -40°C to 71°C
Operation -15°C to 40°C -40°C to 71°C
Charge with TC -15°C to 50°C -40°C to 71°C
Charge without TC 0°C to 40°C -15°C to 50°C
Terminal Torque Specifications
Terminal Type ft-lbs in-lbs Nm
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) 4.2 - 6.14 50-84 5.6 - 7.23
FR45 6.0 - 7.19 70-104 7.9 - 10.15
M8 | LT 7.1 - 8.14 85-109 9.6 - 10.21
DT (stud) | M10M (stud) 9.2 - 10.18 110-139 12.2 - 14.14
  Name Size
Charging Instructions Icon Charging Instructions 1.1 MB
Installation Manual Icon Installation Manual 1.7 MB
Spec-sheet Icon Spec-sheet 1.5 MB
Product Menu