FT1050-30H
  • 12-volts
  • 30H Group Size
  • 242 mins @ 25 amps
  • 45 mins @ 75 amps
  • 90 AH @ 5HR
  • 105 AH @ 20HR
  • 1300 CA @ 32°C
  • 1050 CCA @ 0°C
FT1050-30H

FT1050-30H High Capacity Dual Purpose AGM Battery

Cycling Capacity
20 hour rate 105 Amp Hours
Reserve Capacity
@ 25 Amps 242 minutes @ 75 Amps 45 minutes
Mechanical Specifications
Group Size 30H
Terminal Type M8 (w/ TP28 Brass AP Included)
Total Height 8.66" (220 mm)
Height 8.43" (214 mm)
Width 6.77" (172 mm)
Length 12.91" (328 mm)
Weight 75.0 lbs (34 kg)
Case Type ABS Plastic - Flame Res Rating UL94-HB
Discharge Table (Constant Current)
Time Amps Rate
20 hr 5.3 0.05 CA
10 hr 9.5 0.1 CA
8 hr 11.4 0.13 CA
5 hr 17.2 0.25 CA
3 hr 25 0.33 CA
2 hr 36 0.5 CA
1 hr 65 1 CA
Electrical Specifications
Nominal Voltage 12 Volt
Capacity @ 100 hour rate 116 AH
Capacity @ 20 hour rate 105 AH
Capacity @ 10 hour rate 100 AH
Capacity @ 5 hour rate 90 AH
CCA 1050
CA or MCA 1300
Short Circuit Current 5000 Amps
Internal Resistance 2.2m Ω
Charge Voltages
Battery Voltages
Charge Stage 12V 24V 36V 48V
Bulk 14.7 V 29.4 V 44.1 V 58.8 V
Absorption 14.7 V 29.4 V 44.1 V 58.8 V
Float 13.6 V 27.2 V 40.8 V 54.6 V
TC Factor: -4mV/°C/cell
Temperature Range Specifications
Condition Recommended Maximum
Storage -15°C to 50°C -40°C to 71°C
Operation -15°C to 40°C -40°C to 71°C
Charge with TC -15°C to 50°C -40°C to 71°C
Charge without TC 0°C to 40°C -15°C to 50°C
Terminal Torque Specifications
Terminal Type ft-lbs in-lbs Nm
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) 4.2 - 6.12 50-82 5.6 - 7.21
FR45 6.0 - 7.17 70-102 7.9 - 10.13
M8 | LT 7.1 - 8.12 85-107 9.6 - 10.19
DT (stud) | M10M (stud) 9.2 - 10.16 110-137 12.2 - 14.12
  Name Size