DC335-6
  • 6-volts
  • J305 Group Size
  • 751 mins @ 25 amps
  • 184 mins @ 75 amps
  • 274 AH @ 5HR
  • 335 AH @ 20HR
  • 1560 CA @ 32°C
  • 1300 CCA @ 0°C
DC335-6

DC335-6 Deep-Cycle AGM Battery

Cycling Capacity
20 hour rate 335 Amp Hours
Reserve Capacity
@ 25 Amps 751 minutes @ 75 Amps 184 minutes
Mechanical Specifications
Group Size J305
Terminal Type DT (Dual AP & Stud)
Total Height 14.41" (366 mm)
Height 13.62" (346 mm)
Width 7.01" (178 mm)
Length 11.61" (295 mm)
Weight 102.7 lbs (46.6 kg)
Case Type ABS Plastic - Flame Res Rating UL94-HB
Discharge Table (Constant Current)
Time Amps Rate
20 hr 16.8 0.05 CA
10 hr 30 0.1 CA
8 hr 36.4 0.13 CA
5 hr 54.8 0.25 CA
3 hr 73.9 0.33 CA
2 hr 102 0.5 CA
1 hr 184 1 CA
Electrical Specifications
Nominal Voltage 6 Volt
Capacity @ 100 hour rate 370 AH
Capacity @ 20 hour rate 335 AH
Capacity @ 10 hour rate 300 AH
Capacity @ 5 hour rate 274 AH
CCA 1300
CA or MCA 1560
Short Circuit Current 5570 Amps
Internal Resistance 1.6m Ω
Charge Voltages
Battery Voltages
Charge Stage 12V 24V 36V 48V
Bulk 14.7 V 29.4 V 44.1 V 58.8 V
Absorption 14.7 V 29.4 V 44.1 V 58.8 V
Float 13.6 V 27.2 V 40.8 V 54.6 V
TC Factor: -4mV/°C/cell
Temperature Range Specifications
Condition Recommended Maximum
Storage -15°C to 50°C -40°C to 71°C
Operation -15°C to 40°C -40°C to 71°C
Charge with TC -15°C to 50°C -40°C to 71°C
Charge without TC 0°C to 40°C -15°C to 50°C
Terminal Torque Specifications
Terminal Type ft-lbs in-lbs Nm
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) 4.2 - 6.0 50-70 5.6 - 7.9
FR45 6.0 - 7.5 70-90 7.9 - 10.1
M8 | LT 7.1 - 8.0 85-95 9.6 - 10.7
DT (stud) | M10M (stud) 9.2 - 10.4 110-125 12.2 - 14.0
Product Menu