DC260-12
  • 12-volts
  • 8D Group Size
  • 578 mins @ 25 amps
  • 145 mins @ 75 amps
  • 214 AH @ 5HR
  • 260 AH @ 20HR
  • 1830 CA @ 32°C
  • 1525 CCA @ 0°C
DC260-12

DC260-12 Deep-Cycle AGM Battery

Cycling Capacity
20 hour rate 260 Amp Hours
Reserve Capacity
@ 25 Amps 578 minutes @ 75 Amps 145 minutes
Mechanical Specifications
Group Size 8D
Terminal Type L (Flag) or APW (Dual Marine)
Total Height 8.82" (224 mm)
Height 8.66" (220 mm)
Width 10.59" (269 mm)
Length 20.51" (521 mm)
Weight 170.6 lbs (77.4 kg)
Case Type ABS Plastic - Flame Res Rating UL94-HB
Discharge Table (Constant Current)
Time Amps Rate
20 hr 13 0.05 CA
10 hr 23.4 0.1 CA
8 hr 28.3 0.13 CA
5 hr 42.3 0.25 CA
3 hr 58.9 0.33 CA
2 hr 78.3 0.5 CA
1 hr 148 1 CA
Electrical Specifications
Nominal Voltage 12 Volt
Capacity @ 100 hour rate 286 AH
Capacity @ 20 hour rate 260 AH
Capacity @ 10 hour rate 234 AH
Capacity @ 5 hour rate 214 AH
CCA 1525
CA or MCA 1830
Short Circuit Current 5810 Amps
Internal Resistance 1.8m Ω
Charge Voltages
Battery Voltages
Charge Stage 12V 24V 36V 48V
Bulk 14.7 V 29.4 V 44.1 V 58.8 V
Absorption 14.7 V 29.4 V 44.1 V 58.8 V
Float 13.6 V 27.2 V 40.8 V 54.6 V
TC Factor: -4mV/°C/cell
Temperature Range Specifications
Condition Recommended Maximum
Storage -15°C to 50°C -40°C to 71°C
Operation -15°C to 40°C -40°C to 71°C
Charge with TC -15°C to 50°C -40°C to 71°C
Charge without TC 0°C to 40°C -15°C to 50°C
Terminal Torque Specifications
Terminal Type ft-lbs in-lbs Nm
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) 4.2 - 6.0 50-70 5.6 - 7.9
FR45 6.0 - 7.5 70-90 7.9 - 10.1
M8 | LT 7.1 - 8.0 85-95 9.6 - 10.7
DT (stud) | M10M (stud) 9.2 - 10.4 110-125 12.2 - 14.0