DC160-8
  • 8-volts
  • GC8 Group Size
  • 315 mins @ 25 amps
  • 131 AH @ 5HR
  • 160 AH @ 20HR
  • 1050 CA @ 32°C
  • 865 CCA @ 0°C
DC160-8

DC160-8 Deep-Cycle AGM Battery

Cycling Capacity
20 hour rate 160 Amp Hours
Reserve Capacity
@ 25 Amps 315 minutes @ 75 Amps 0 minutes
Mechanical Specifications
Group Size GC8
Terminal Type M8
Total Height 10.71" (272 mm)
Height 10.55" (268 mm)
Width 7.17" (182 mm)
Length 10.24" (260 mm)
Weight 71.2 lbs (32.3 kg)
Case Type ABS Plastic - Flame Res Rating UL94-HB
Discharge Table (Constant Current)
Time Amps Rate
20 hr 8 0.05 CA
10 hr 14.4 0.1 CA
8 hr 17.4 0.13 CA
5 hr 25.7 0.25 CA
3 hr 39.2 0.33 CA
2 hr 56.1 0.5 CA
1 hr 90.2 1 CA
Electrical Specifications
Nominal Voltage 8 Volt
Capacity @ 100 hour rate 176 AH
Capacity @ 20 hour rate 160 AH
Capacity @ 10 hour rate 144 AH
Capacity @ 5 hour rate 131 AH
CCA 865
CA or MCA 1050
Short Circuit Current 2330 Amps
Internal Resistance 2.4m Ω
Charge Voltages
Battery Voltages
Charge Stage 12V 24V 36V 48V
Bulk 14.7 V 29.4 V 44.1 V 58.8 V
Absorption 14.7 V 29.4 V 44.1 V 58.8 V
Float 13.6 V 27.2 V 40.8 V 54.6 V
TC Factor: -4mV/°C/cell
Temperature Range Specifications
Condition Recommended Maximum
Storage -15°C to 50°C -40°C to 71°C
Operation -15°C to 40°C -40°C to 71°C
Charge with TC -15°C to 50°C -40°C to 71°C
Charge without TC 0°C to 40°C -15°C to 50°C
Terminal Torque Specifications
Terminal Type ft-lbs in-lbs Nm
AP | DT (AP) | M6 | M6M (stud) | TP07 (AP) | TP08 (AP) 4.2 - 6.0 50-70 5.6 - 7.9
FR45 6.0 - 7.5 70-90 7.9 - 10.1
M8 | LT 7.1 - 8.0 85-95 9.6 - 10.7
DT (stud) | M10M (stud) 9.2 - 10.4 110-125 12.2 - 14.0